| Measuring range (Qmin to Qmax) | 20-400 l/min (5.3 to 105.7 gpm) |
| Accuracy (± 1 σ) in water, 0-120 °C (32-248 °F) | ± 1 % FS |
| Response time (63.2 %) | < 1 s |
| Measuring range (Tmin to Tmax) | 0-120 °C (32-248 °F) |
| Accuracy (± 1 σ), 15-90 °C (59-194 °F) | ± 0.5 K |
| Accuracy (± 1 σ), 0-120 °C (32-248 °F) | ± 1 K |
| Response time (63.2 % at 50 % FS flow) | 250 ms |
| Liquid types | Aqueous media compatible with wetted materials. Kinematic viscosity ≤ 2 mm2/s (cSt) |
| Liquid temperature, operation | Water: 0-100 °C (32-212 °F) |
| Liquid temperature, peak | -25 °C (-13 °F), non-freezing 120 °C (248 °F) for 5 minutes, up to 3 weeks in sensor lifetime |
| Ambient temperature, operation | -25 to +60 °C (-13 to +140 °F) |
| Ambient temperature, peak | -55 to +90 °C (-67 to +194 °F) |
| Humidity, relative | 0-95 %, non-condensing |
| Maximum system pressure | 24 bar (348 psig) |
| Altitude | Max. 2000 m.a.s.l. |
| Power supply | 5 VDC (± 5 %), PELV Grounding of sensor supply required |
| Output signals | Ratiometric |
| Digital output signals | Grundfos open data protocol |
| Analog output signals | 0.5 – 3.5 V for flow (0.5 V at 20 l/min, 3.5 V at 400 l/min) 0.5 – 4.1 V for temperature (0.5 V at 0 °C, 4.1 V at 120 °C) |
| Power consumption | Appr. 75 mW |
| Maximum cable length | 3 m (9.10 ft) |
| Sensing element | Silicon-based MEMS |
| Sealing | EPDM O-rings, FKM O-rings or EPDM sealing sleeve with FKM O-rings |
| Housing | Composite (PPS, PA66) |
| Flow pipe | PPA 40-GF |